Brivis Error Code 36

Error Code h01 36: Bad Supply Air Thermistor Location. The temperature registered by the supply-air did not reach the modulation set point temperature defined by installer setting number 6 within the main fan override time defined by factory parameter number 8.

Need help with your Brivis System?

    Please select accurately so we can provide you with the best service providers in your immediate vicinity.



    Call us at: 1300665137
    Or send us an email at: [email protected]

     

    Brivis Fault Code 36

    Brivis Error Code 36 Bad Supply Air Thermistor Location: The temperature registered by the supply-air did not reach the modulation set point temperature defined by installer setting number 6 within the main fan override time defined by factory parameter number 8.

    For Heater Repair Tech Only

    Reason: BAdSA_THM means, the supply air thermistor has a circuit, but has not reached 30oC. Within 2 minutes of the fan operation commencing, in a normal heating cycle. Operation Mode: The user still has some heating, until the problem can be rectified by a service technician, though the operation does not give the maximum or best performance. In BAdSA_THM fan operation, the unit cannot rely on the thermistor signal, and therefore operates the heater as follows: Fan operates at installer set speed, and the gas valve operates at minimum rate. The fan ON time = 45 seconds from when the gas valve is energised at the start of the heating cycle. The fan OFF time = 60 seconds from when the gas valve closes at the end of the heating cycle. Service Check List: • Check the Supply Air Thermistor is installed in the Supply Air duct • Check the thermistor is not faulty, check that the resistance is approx 10 kΩ @ 20oC. • Check the Supply Air Thermistor is not located in an unsuitable position within the Supply Air duct.

    SKU: 311 Category: Tags: ,