Braemar Fault Code 22
Fault: Supply voltage out of range.
Potential Cause (Technical Use Only: Potential remedy):
- Partial power supply interruption – “brown out”. Check electricity supply history with customer.
- Reduced electricity supply. Check heater supply voltage with heater and all other electrical appliances running. Arrange to have supply upgraded if required.
- Faulty heater transformer. Check transformer with heater operating ‐ should have approx. 24Vac out with 240Vac in
For Braemar Ecostar TQ, TQM, TQS, TQMD, BMQ Gas Ducted Heaters and Braemar Supernova TQS Gas Ducted Heaters.