Braemar Error Code 7

Fault Code 7: Ignition failure

Need help with your Braemar System?

    Please select accurately so we can provide you with the best service providers in your immediate vicinity.



    Call us at: 1300665137
    Or send us an email at: [email protected]

     

    Braemar Fault Code 07

    Fault: Ignition failure

    Potential Cause (Technical Use Only: Potential remedy):

    • OT3 open (if fitted – located on burner cover).  Check switch – if open, button will click when pressed.
    • Ignition cable damaged or disconnected. Check ignition lead – re‐connect or replace if required.
    • Incorrect spark gap. Check spark gap between ignition electrode and burner face – adjust to 3‐4mm if required.
    • Incorrect test point pressure. Check pressure at outlet pressure test point on gas valve – compare with value specified on data label.
    • Incorrect gas supply pressure to heater. Check supply pressure at inlet pressure tapping on gas valve with heater on max and all other gas appliances running. -NG – minimum 1.13 kPa. -Propane – minimum 2.75 kPa. Check gas meter regulator outlet pressure and fitting line size and length.
    • Gas supply turned off at gas meter, heater isolation valve or gas valve on/off switch. Check gas supply – turn on if required.
    • ICS not detecting flame – ignition occurs but gas off after approx. 7 seconds. Check flame sense lead is connected at ICS. Check flame sense lead is not damaged or shorted – replace if required. Check flame sense gap – should be 4‐ 6mm from flame sense electrode to burner face. Check flame sense electrode is clean – clean with steel wool or replace if required.

     


    For Braemar Ecostar TQ, TQM, TQS, TQMD, BMQ Gas Ducted Heaters and Braemar Supernova TQS Gas Ducted Heaters.