Braemar Error Code 13

Fault Code 13: PS high closed at start.  Condensate blocking combustion fan suction hose. Faulty pressure switch, contacts stuck closed.

Need help with your Braemar System?

    Please select accurately so we can provide you with the best service providers in your immediate vicinity.



    Call us at: 1300665137
    Or send us an email at: [email protected]

     

    Fault Code 13

    Fault: PS high failed to close. Combustion fan not operating. Combustion fan motor or fan wheel dislodged or jammed. Combustion fan suction hose disconnected or damaged.

    Potential Cause (Technical Use Only: Potential remedy):

    • Combustion fan suction hose disconnected or damaged.  Re‐connect or replace combustion fan suction hose. 
    • Flue system blockage.  Check and clear blockage. 
    • Combustion fan blocked.  Check and un‐block combustion fan. 
    • Condensate blocking combustion fan suction hose.  Clear blockage.  Check flue condensate drain fitted correctly (condensing models only). 
    • Swarf obstructing combustion fan pressure tapping.  Check both ends of pressure tapping – clear obstruction or replace pressure tapping. 
    • Faulty pressure switch – contacts stuck open.  Check suction pressure – if sufficient, and pressure switch does not close, replace pressure switch.
    • Flue cowl pushed on too far.  Check and re‐fit flue cowl.

     


    For Braemar Ecostar TQ, TQM, TQS, TQMD, BMQ Gas Ducted Heaters and Braemar Supernova TQS Gas Ducted Heaters.