Brivis Error Code 51

Error Code h01 51: Rollout No Gas. With no gas being expelled and no ignition source active a flame rollout signal has been detected indicating a problem with the flame rollout sensing circuitry.

Need help with your Brivis System?

    Please select accurately so we can provide you with the best service providers in your immediate vicinity.



    Call us at: 1300665137
    Or send us an email at: [email protected]

     

    Brivis Fault Code 51

    Brivis Error Code 51 Rollout No Gas: With no gas being expelled and no ignition source active a flame rollout signal has been detected indicating a problem with the flame rollout sensing circuitry.

    For Heater Repair Tech Only

    Reason: This error indicates that the AFRO circuit has detected a flame rollout while the gas valve is not energised, and flame is not expected. Service Check List: • Check that the pilot AFRO bar or wiring is not shorted to Earth. • Check if a flame is present with the unit turned OFF. • Check the gas valve is not jammed open due to malfunction, obstruction or blockage. • Check if the 24 Volt power supply to the valve has been turned OFF, as expected in the normal operation.